Lesson 88 ข้อแนะนำจากต่างประเทศ เรื่องการกรอกข้อมูลสำหรับ รายละเอียดการสั่งซื้อ BATTERTY MONITORING ยี่ห้อ Powershield

SNMP over TCP/IP comes as standard

You selection of RS485 is correct for Modbus RTU communication option

  1. It is important to untick this box so it shows red note that will help you to complete the Form
  1. Please indicate the PO number so we know which project it is related to.
  1. To be able to get auto chacking, it is important to indicate the number of strings/ number of blocs / voltage so it select the right P/N
  1. Tag washer is 3 per blocks with dual mSensor and 4 for Single mSensor. Here you have 40 Blocks all with Dual mSensor so it should be 1x40x3=120 Tags so I put 150
  1. As you have only 1 string, no need to select Hub topology

Once you completed the form and all Red Notice have been removed then you can click

I attached the revised System Form.

https://drive.google.com/file/d/1QXkn_WqwnzRaMA7EE5DQVsLOwgA1JnJj/view?usp=drive_link